Catalog navigation
Choix du modèle CAO
Produit(s) sélectionnable(s): 9
HELP_VARIABLE
Company
Cooper Crouse-Hinds EU
Description
GHG 981 0048 25 - Ex-Safety switch 25 A for Zone 22
Bill of material
GHG9810048R1214
IDNR
Article number
LOD
Level of Detail
POL
Pole Configuration
NT
Description
Ex-Safety switch 25 A for Zone 22
T1
Marking accd. to 2014/34/EU
<Ex> II 3 D Ex tc IIIC T80 °C - 95 °C Dc
T2
Type Examination Certificate
CCH 15 ATEX 1001
T3
-
-
T4
Permissible ambient temperature
-55 °C bis +55 °C
T5
Rated voltage
up to max. 690 V
T6
Rated current
max. 25 A
T7
Rated making / Rated breaking capacity AC3 accd. EN 60947-3
Ue 230 V / Ie 20 A, Ue 400 V / Ie 20 A, Ue 500 V / Ie 16 A, Ue 690 V / Ie 10 A
T8
Version
Standard version
T9
-
-
T10
Degree of protection accd. to EN 60529
IP66
T11
Cable entries / thread
T12
Connecting terminals
4 mm² - 10 mm²
T13
Enclosure material
T14
Weight
T15
Enclosure colour
Plastic = black / sheet steel = RAL 7032 / stainless steel 316L = electro-polished
T16
Product description
TP
Text for product group
CEAG safety switches GHG 262 up to 20 A combines advanced safety with high AC-3 switching capacity and innovative design. Emergency-STOP version accd. EN 60204-1 as well as Class 1 accd. to IEC 60947-3 completes the technical features of this series.