Catalog navigation
CAD model selection
Selectable products: 9
HELP_VARIABLE
Company
Cooper Crouse-Hinds EU
Description
GHG 981 0048 25 - Ex-Safety switch 25 A for Zone 22
Bill of material
GHG9810048R1214
IDNR
Article number
LOD
Level of Detail
POL
Pole Configuration
NT
Description
Ex-Safety switch 25 A for Zone 22
T1
Marking accd. to 2014/34/EU
<Ex> II 3 D Ex tc IIIC T80 °C - 95 °C Dc
T2
Type Examination Certificate
CCH 15 ATEX 1001
T3
-
-
T4
Permissible ambient temperature
-55 °C bis +55 °C
T5
Rated voltage
up to max. 690 V
T6
Rated current
max. 25 A
T7
Rated making / Rated breaking capacity AC3 accd. EN 60947-3
Ue 230 V / Ie 20 A, Ue 400 V / Ie 20 A, Ue 500 V / Ie 16 A, Ue 690 V / Ie 10 A
T8
Version
Standard version
T9
-
-
T10
Degree of protection accd. to EN 60529
IP66
T11
Cable entries / thread
T12
Connecting terminals
4 mm² - 10 mm²
T13
Enclosure material
T14
Weight
T15
Enclosure colour
Plastic = black / sheet steel = RAL 7032 / stainless steel 316L = electro-polished
T16
Product description
TP
Text for product group
CEAG safety switches GHG 262 up to 20 A combines advanced safety with high AC-3 switching capacity and innovative design. Emergency-STOP version accd. EN 60204-1 as well as Class 1 accd. to IEC 60947-3 completes the technical features of this series.
Additional Information
Recommendations
Similar parts
Related Equipment
Additional Data
Catalog Vendor Locations
Users who viewed this, were also interested in
Previews
3D
Dimension
2D
Download CAD models